For predictive maintenance purposes, which of the following are the main input parameters used by the algorithm that predicts the remaining lifespan of the capacitor in a UPS power module?

Choose three
Explanation

Electrolytic capacitors in UPS power modules degrade primarily due to thermal stress and electrical stress. Operating temperature accelerates the evaporation of the electrolyte inside the capacitor, shortening its service life according to well-established thermal aging models. Ripple current/voltage passing through the capacitor generates internal heating via the equivalent series resistance (ESR), which further accelerates aging. The load rate of the power module determines the current stress placed on the capacitor and influences both its operating temperature and the ripple current it experiences. Rotational speed pertains to fan or motor components rather than capacitor aging, so it is not used as an input parameter for this specific prediction algorithm.