The "3 zero" hardware-clamping technology used in S-ECO mode is built around three zero-delay mechanisms: no inverter start-up delay and no inter-module communication delay (0 delay); no need to wait for mains-abnormality detection or for the mains voltage zero-crossing point before transferring (0 waiting); and continuous zero-voltage-difference hot backup, where the standby inverter output is hardware-clamped to match the bypass voltage at all times so the changeover is seamless (0 voltage hot backup). This combination is what allows the UPS to transfer between bypass/ECO and inverter (battery) mode in 0 ms with no output interruption, as described in Huawei's UPS S-ECO mode documentation. "0 current hot backup" is not part of this defined technology, since the clamping mechanism operates on output voltage matching rather than current matching.