QuestionQ86

VerifiedInstall the solution

You are installing a pair of HPE Aruba Networking CX 8325-48Y8C switches with front-to-back airflow in a rack that already contains servers and storage arrays whose bezel locks and drive bays face the front.

What is the best mounting approach?

Explanation

Front-to-back airflow equipment must draw cooling air from the cold aisle at the rack front and exhaust it toward the hot aisle at the rear. Aligning the switches with the front-facing servers and storage maintains a consistent rack airflow path and avoids recirculating hot exhaust air. HPE Aruba documentation identifies a front-to-back airflow version of the 8325-48Y8C and directs installers to verify that the product airflow configuration supports the data center cooling design.