QuestionQ26

VerifiedIntroduction to Huawei Data Center Facility and Critical Power Solutions

Which of the following statements about the Huawei high-temperature chilled water fan wall are correct?

Choose three
Explanation

Huawei's high-temperature chilled water fan wall (e.g., FusionCol8000-C) integrates PFC harmonic suppression in its EHU/power-driver module rather than in a component called 'DG,' so the PFC claim tied to 'DG' does not correctly describe this product. The solution's main control unit, fan drive unit, low-voltage power supply unit, and fan unit use a modular design that supports hot swapping and 1-minute quick maintenance, as stated in Huawei's product documentation. Because the fan wall uses horizontal (side) airflow rather than traditional under-floor downflow distribution, it eliminates the need for a raised floor, lowering construction/cooling investment (Capex). Additionally, raising the chilled-water inlet temperature from the traditional 15°C to 20°C used in high-temperature fan wall designs reduces chiller power consumption/load (CLF) by about 15%, improving overall cooling system energy efficiency.