When an Energy Storage System (ESS) fire alarm activates but only smoke — not flame — is being emitted, which of the following is the correct response action?

Explanation

With an ESS emitting only smoke and no visible flame, responders should not open the enclosure or spray water directly inside it, since doing so risks igniting accumulated flammable off-gases or causing an electrical hazard. The correct procedure is to keep a safe distance and continue monitoring the unit, refrain from injecting water into the enclosure until flame is confirmed, but apply water to the exterior surface to help cool the unit and slow any thermal runaway progression; water should only be sprayed directly into the unit once open flame is observed, since only then is direct suppression appropriate and safer.