A data center is designed to increase cooling capacity and reduce operating costs by using a Cold Aisle Containment deployment.

Which statement is true about switch placement in this scenario?

Explanation

Cold-aisle containment requires a switch’s air intake to face the cold aisle and its exhaust to face the hot aisle. Switches may be mounted with ports at either the front or rear of a rack, but the installed fan and power-supply modules must provide the required airflow direction. A rear-mounted switch therefore needs back-to-front airflow hardware, whereas a front-mounted switch can use front-to-back airflow.